.:: Jasa Membuat Aplikasi Website,Desktop,Android Order Now..!! | | Order Now..!! Jasa Membuat Project Arduino,Robotic,Print 3D ::.

Communication between Mitsubishi FX3U PLC and SCADA via RS485BD

0 komentar


بِسْــــــــــــــــمِ اﷲِالرَّحْمَنِ اارَّحِيم
bismillaahirrahmaanirrahiim

السَّلاَمُ عَلَيْكُمْ وَرَحْمَةُ اللهِ وَبَرَكَاتُهُ
Assalamu'alaikum warahmatullahi wabarakatuh

Hi Friends, Here i want share with you a tutorial on how to establish Communication between Mitsubishi FX3U PLC and Elipse SCADA via RS485 BD 


The required Items for the setup is as follows


Sr. no.
Material
1
PLC Type : FX Series
2
CPU      : FX3U
3
Module   : FX3U RS485BD
4
SCADA Make : Elipse
5
SCADA Type : 20/300/ Unlimited Tags
6
Other





Figure Connection between PC(SCADA) & PLC(FX3U)


 The required cables are as follows

 

Sr. no.
Item
Description
1
Medoc cable
(MITSU-CAB2A)
Prog. cable for FX PLC
2
Converter Cables
*1
Comm. Cable for PC ,PLC &
Converter

 *1 To connect the SCADA to the controller the RS 232 to RS 485 Converter  is used. The Converter is having RS422/485 port for connecting to PLC & RS232 port on other side for connection to PC.



As the FX-485BD Port is used, PLC parameter settings are required on PLC side.
PLC Parameter Configuration for Channel1:
1. Baud Rate: 9600.
2. Data Bits: 7 bits
3. Parity : Even
4. Stop Bit: 1 bit
5. Sum Check: Yes
6. Transmission Control: Without CR, LF
7. H/W Type: RS485
8. Station No.: 01
PLC Communication Parameter Settings using GX Developer:

PLC Communication Parameter Settings using GX Developer

 SCADA Program settings



 SCADA Driver Details:

 

Driver
MELSEC-A.dll
Version
1.02
Latest Update
2004.10.20
Driver Help
Melsec-A_US.pdf

 

Driver Setting Parameters:
P1: 1 (Comm. Port)
P2: 3721(Comm. Parameters: 9600 bps, 7 data bits, Even
Parity & 1 stop bit)
P3: 300 (Timeout in milliseconds)
P4: 10 (For RS485)
Other needed Configuration is done through �Extra  Configuration �Dialog as follows:



� Snap shot of Driver Settings in Elipse SCADA software
 

Step 1: Enter the Driver Parameters P1-P4.



Driver Parameters
Step 2: Click on �Extra� button to edit settings.



 Step3: In �Extra� menu select �Protocol� option to edit Protocol  Settings.


�Protocol� option

 Tag Addressing Parameters:
 

The Tags are generated by using N1-N4 parameter settings as follows:
 

N1: Station Number (e.g.: 1)

N2: CPU Number (normally 255)

N3: Variable Type (e.g.: 14 for D Register)

N4: Variable Address (e.g.:10 for D10 Register)

Scan: User Defined
 

� Snap shot of Tag Addressing Parameters in Software
 
Tag Addressing Parameters

If you like the this Tutorial on PLC please Share this.
 

Update Contact :
No Wa/Telepon (puat) : 085267792168
No Wa/Telepon (fajar) : 085369237896
Email : Fajarudinsidik@gmail.com
NB :: Bila Sobat tertarik Ingin membuat software, membeli software, membeli source code, membeli hardware elektronika untuk kepentingan Perusahaan maupun Tugas Akhir (TA/SKRIPSI), Insyaallah Saya siap membantu, untuk Respon Cepat dapat menghubungi kami, melalui :

No Wa/Telepon (puat) : 085267792168
No Wa/Telepon (fajar) : 085369237896
Email: Fajarudinsidik@gmail.com


atau Kirimkan Private messanger melalui email dengan klik tombol order dibawah ini :

ٱلْحَمْدُ لِلَّهِ رَبِّ ٱلْعَٰلَمِين
Alhamdulilah hirobil alamin

وَ السَّلاَمُ عَلَيْكُمْ وَرَحْمَةُ اللهِ وَبَرَكَاتُهُ
wassalamualaikum warahmatullahi wabarakatuh


Artikel Communication between Mitsubishi FX3U PLC and SCADA via RS485BD, Diterbitkan oleh scodeaplikasi pada Senin, 26 Maret 2012. Semoga artikel ini dapat menambah wawasan Anda. Website ini dipost dari beberapa sumber, bisa cek disini sumber, Sobat diperbolehkan mengcopy paste / menyebar luaskan artikel ini, karena segala yang dipost di public adalah milik public. Bila Sobat tertarik Ingin membuat software, membeli software, membeli source code ,Dengan Cara menghubungi saya Ke Email: Fajarudinsidik@gmail.com, atau No Hp/WA : (fajar) : 085369237896, (puat) : 085267792168.

Tawk.to